The Eos range of VRLA batteries uses AGM technology and is built to the IEC 60896-21/22 standard. It gives 100% capacity out of the box, can handle deep discharges, and has a design life of more than 15 years with a cycle life of more than 1200 cycles to 80% depth of discharge. Flexible connectors and several optional racking systems allow many ways of installing it. The Eos-2000 is a single 2 V cell of 2000 Ah at the 10-hour rate, for fixed and mobile telecoms, UPS, utilities and solar.
The Narada Eos-2000 2V 2000Ah VRLA battery is an AGM battery cell for fixed power systems. Its industrial VRLA battery design suits UPS battery banks, telecom and utility backup applications.
Capacity at different rates
The capacity of the Eos-2000 at 25 °C depends on the discharge rate.
| Rate | Discharge current | End voltage per cell | Capacity |
|---|---|---|---|
| 10 hour | 200 A | 1.80 V | 2000 Ah |
| 3 hour | 500 A | 1.80 V | 1500 Ah |
| 1 hour | 1100 A | 1.75 V | 1100 Ah |
Constant current discharge
Discharge current in amperes to the end voltage shown, at 25 °C (77 °F).
| End voltage per cell | 5 min | 15 min | 30 min | 45 min | 1 h | 2 h | 3 h | 4 h | 5 h | 6 h | 8 h | 10 h | 12 h | 24 h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60 V | 2896 | 2437 | 1980 | 1560 | 1305 | 802 | 589 | 463 | 385 | 332 | 260 | 215 | 183 | 99.7 |
| 1.65 V | 2715 | 2293 | 1806 | 1447 | 1232 | 779 | 573 | 456 | 380 | 328 | 257 | 214 | 182 | 98.2 |
| 1.70 V | 2552 | 2170 | 1651 | 1356 | 1170 | 752 | 547 | 441 | 371 | 320 | 254 | 210 | 180 | 97.8 |
| 1.75 V | 2407 | 2043 | 1523 | 1279 | 1105 | 725 | 535 | 431 | 364 | 315 | 250 | 209 | 179 | 96.9 |
| 1.80 V | 2274 | 1905 | 1426 | 1207 | 1049 | 703 | 523 | 424 | 356 | 309 | 246 | 206 | 177 | 94.9 |
| 1.83 V | 2106 | 1754 | 1331 | 1142 | 990 | 673 | 507 | 412 | 350 | 305 | 244 | 205 | 176 | 94.9 |
| 1.85 V | 1953 | 1620 | 1253 | 1063 | 927 | 634 | 479 | 392 | 334 | 292 | 236 | 198 | 169 | 92.2 |
| 1.90 V | 1599 | 1279 | 1041 | 888 | 766 | 530 | 428 | 356 | 302 | 265 | 214 | 180 | 156 | 86.0 |
| 1.94 V | 1440 | 1163 | 956 | 805 | 689 | 473 | 367 | 309 | 266 | 234 | 192 | 163 | 140 | 76.6 |
Constant power discharge
Discharge power in watts per cell to the end voltage shown, at 25 °C (77 °F).
| End voltage per cell | 5 min | 15 min | 30 min | 45 min | 1 h | 2 h | 3 h | 4 h | 5 h | 6 h | 8 h | 10 h | 12 h | 24 h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.60 V | 4923 | 4142 | 3423 | 2899 | 2497 | 1588 | 1178 | 950 | 802 | 705 | 574 | 475 | 400 | 214 |
| 1.65 V | 4752 | 4013 | 3291 | 2777 | 2418 | 1522 | 1148 | 931 | 782 | 689 | 561 | 463 | 390 | 208 |
| 1.70 V | 4594 | 3907 | 3183 | 2679 | 2327 | 1462 | 1125 | 907 | 766 | 673 | 552 | 459 | 387 | 207 |
| 1.75 V | 4406 | 3738 | 2992 | 2512 | 2194 | 1398 | 1103 | 891 | 752 | 653 | 541 | 455 | 383 | 205 |
| 1.80 V | 4208 | 3524 | 2797 | 2341 | 2020 | 1346 | 1069 | 877 | 733 | 640 | 529 | 447 | 377 | 201 |
| 1.83 V | 3960 | 3297 | 2614 | 2182 | 1889 | 1297 | 1045 | 853 | 713 | 622 | 515 | 440 | 370 | 198 |
| 1.85 V | 3710 | 3079 | 2416 | 2000 | 1731 | 1247 | 1010 | 830 | 693 | 604 | 499 | 424 | 357 | 191 |
| 1.90 V | 3119 | 2495 | 1975 | 1640 | 1467 | 1125 | 921 | 768 | 647 | 570 | 467 | 399 | 336 | 179 |
| 1.94 V | 2822 | 2279 | 1745 | 1441 | 1323 | 1036 | 842 | 700 | 590 | 513 | 420 | 359 | 302 | 162 |
Racking (optional)
Narada racks are made of powder-coated steel tubing, are easy to assemble and come complete with sliding cover terminal (take-off) plates. The figures below are for 24 Eos-2000 cells in a 48 V system.
| Cell configuration | Rack width* | Rack depth | Rack height | System weight |
|---|---|---|---|---|
| 2 high, 12 wide | 3195 mm | 562 mm | 880 mm | 3200 kg |
| 4 high, 6 wide | 1640 mm | 562 mm | 1680 mm | 3240 kg |
Source: manufacturer datasheet Eos-2000-04-N-EN (Ver.05, April 2015), Narada Power Source Co., Ltd. Subject to revision without prior notice. The outline dimensions are in the drawing on the datasheet; download it with the button above.