About this item

  • Output: 20 kVA / 16 kW, 400 V three-phase, configurable for 380, 400 or 415 V nominal output voltage
  • Online double conversion: sine-wave output with less than 5% voltage distortion at full load and 95.3% efficiency at full load
  • Bypass: built-in maintenance bypass and static bypass, with parallel capability
  • Batteries: four VRLA battery modules ship installed, with a typical recharge time of 5 hours and an expected battery life of 3 to 5 years
  • Management: multi-function LCD status and control console, RS-232 and Smart-Slot with the AP9631 network management card, and emergency power off (EPO)
  • Quiet and compact: 51.3 dBA at 1 m in a 1490 × 523 × 842 mm cabinet

Key details

Model SUVTP20KH4B4S
Output
Output power capacity 16.0 kW / 20.0 kVA
Nominal output voltage 400 V three-phase (configurable 380, 400 or 415 V)
Efficiency at full load 95.3%
Output voltage distortion Less than 5% at full load
Output frequency, synchronised to mains 47–53 Hz for 50 Hz nominal

See all technical details

Technical details

Model SUVTP20KH4B4S
Output
Output power capacity 16.0 kW / 20.0 kVA
Nominal output voltage 400 V three-phase (configurable 380, 400 or 415 V)
Efficiency at full load 95.3%
Output voltage distortion Less than 5% at full load
Output frequency, synchronised to mains 47–53 Hz for 50 Hz nominal
Output frequency, not synchronised 50 Hz ±0.1%
Load crest factor 3:1
Topology Double conversion online
Waveform Sine wave
Maximum output current 32 A
Bypass Built-in maintenance bypass, built-in static bypass
Input
Nominal input voltage 400 V three-phase
Input frequency 40–70 Hz (auto-sensing)
Input connection Hard wire, 5-wire (3PH + N + G)
Input voltage range for main operations 304–477 V
Other input voltages 380, 415 V
Maximum input current 27.0 A
Input power factor at full load 0.98
Batteries and runtime
Battery type VRLA
Included battery modules 4
Typical recharge time 5 hours
Nominal battery voltage ±192 V (split battery referenced to neutral)
Expected battery life 3–5 years
Replacement battery cartridges 4
End of discharge battery voltage ±154 V
Communications and management
Interface ports DB-9 RS-232, Smart-Slot
Pre-installed SmartSlot card AP9631 network management card
Control panel Multi-function LCD status and control console
Audible alarm Audible and visible alarms prioritised by severity
Emergency power off (EPO) Yes
Physical
Height 1490 mm
Width 523 mm
Depth 842 mm
Net weight 599 kg
Shipping weight 630 kg
Colour Black
Environment
Operating temperature 0–40 °C
Operating relative humidity 0–95%
Operating elevation 0–1000 m
Storage temperature −50 to 40 °C
Audible noise at 1 m 51.3 dBA
Heat dissipation online 3112 BTU/hr
Protection class IP20
Conformance
Approvals and standards CE, C-tick, RCM, EN 50091-2, EN/IEC 62040-3, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-111
Standard warranty 1 year repair or replace, with start-up service

Product description

Three-phase protection with batteries inside

The Smart-UPS VT is an effective 10–40 kVA three-phase UPS that protects mission-critical applications against downtime and data loss. This 20 kVA unit ships with its battery modules and power modules installed, so it arrives ready to connect.

Online double conversion

The inverter supplies the load continuously, so equipment never runs directly from the mains. The output is a clean sine wave with less than 5% distortion at full load, and the 3:1 crest factor accepts the peaks of electronic loads.

Maintenance and expansion

  • A built-in maintenance bypass lets the UPS be serviced without switching the load off.
  • A built-in static bypass transfers the load automatically if the UPS needs to be taken out of the circuit.
  • Parallel capability allows more capacity or redundancy to be added later.

Management

A multi-function LCD console shows the status and gives local control, and audible and visible alarms are prioritised by severity. The Smart-Slot takes the AP9631 network management card for monitoring over the network, and an RS-232 port and emergency power off are provided.

Price

On request

Pricing and availability are confirmed in your quotation. Tell us the quantity and where it is needed when you ask.

A black desk telephone beside an older dial telephone

Need help choosing?

Tell us the load, the backup time and the site. Our engineers will recommend the right rating and send an itemised quotation.

A black desk telephone beside an older dial telephone

Discuss your power requirements with our engineers

Tell us about the site, the load and the outcome you need. We will come back with a recommendation and a quotation, and an engineer can visit the site to check the roof or open space, the shading and the electrical connection before the design is fixed.